Start With What the Meter Recorded
Base the comparison on the same meter or group of meters and use kWh from actual readings. Reconcile estimated bills against later readings and record the dates that each reading covers. A bill spanning 35 days may record more gas than one spanning 28 days even if daily consumption has fallen. Align the weather data to the reading dates so both records describe the same period.
Write down which equipment the meter covers. A school might use gas for space heating and hot water, and a separate gas supply might serve its kitchen. A meter dedicated to the boilers narrows the scope. If a meter serves other plant as well, ask what changed in those operations during the comparison period. A drop in kitchen use, for instance, can leave less gas on the bill even when the boiler plant is performing as it did before.
Keep tariffs and consumption in separate columns when you prepare the figures. With readings in kWh you can see how much fuel the site used. The unit rate gives those kWh a cash value. Fuel savings can be worth more when the unit rate rises, even as the site’s total gas expenditure increases. For a cost figure the finance team can reproduce, state the rate you used and the billing period it applies to.
How Heating Degree Days Help Verify Boiler Gas Savings
A building normally needs more space heating when the weather is colder. Heating degree days describe how far and for how long the outdoor temperature was below a chosen reference level. A colder day contributes more to the total, and a month with a run of cold days can have a substantially higher total than a mild month. Use the same reference level and weather source on both sides of the comparison.
For the period before installation, plot monthly gas use against the degree days recorded over the corresponding meter dates. Where space heating accounts for a large share of consumption, the colder periods will often sit at the upper end of the gas readings. Use the established relationship to estimate what gas use would have been in the weather experienced after the installation. Compare that expected figure with the amount recorded on the meter.
Some gas use continues through mild weather. A boarding school, for instance, can still need hot water when the space heating is off. A useful comparison allows for use that has little relationship with outdoor temperature, using meter data and what the estates team knows about the equipment. On a combined meter, the team can review mild-period readings and record whether occupancy or hot water use was typical before treating those readings as a guide.
Test how well the baseline accounts for periods you already understand. Look back at a month with ordinary opening hours and compare what the relationship would have predicted with what the meter actually recorded. Then check an unusual period, such as a closure. If the estimates miss ordinary use by an amount similar to the proposed saving, review the dates, loads and assumptions with the analyst. The baseline is useful when it gives you a credible range for what might have happened without the work.
An Example of Weather-Adjusted Gas Savings
Suppose a site used 100,000 kWh in a baseline period. Its analyst estimates that 25,000kWh went to gas uses that were broadly independent of the weather and 75,000kWh went to space heating. In the equivalent period after installation, there are 20% fewer heating degree days. For this illustration, assume that the non-weather-related use stays steady and space-heating consumption moves in proportion to degree days. That gives an expected 85,000 kWh in the milder conditions, made up of 25,000 kWh for the steady uses and 60,000 kWh for space heating.
If the site actually records 78,000 kWh in the latter period, its raw reduction is 22,000 kWh. The weather-adjusted comparison shows 7,000 kWh below the expected 85,000 kWh, or about 8.2%. That is the gap to investigate alongside evidence of boiler operation and any other site changes. The example uses assumed figures to illustrate the arithmetic. A real comparison should use a baseline drawn from the site’s records and check how well the estimate fits those records.
What Happened at Whitehall in February?
Whitehall had two sources of evidence. The school generated Optiburner Savings Reports within a month of installation. The council independently compared the school’s monthly gas readings and used degree-day analysis to allow for differences in outside temperatures. The case study reports that January’s gas use was 28.1% lower than the previous January. The council’s year-wide average saving of around 15.3% describes the wider period covered by its analysis.
In February, the case study reports that the optimiser had been switched off for maintenance and remained off afterwards. The published comparison showed no gas saving for that month. Note the dates when any optimiser at your site was out of operation and ask the person responsible for the plant to confirm when it was back in use. That record can give context to a change in the meter readings.
There are two useful views of such a month. Keep it in a review of actual gas use, because the business paid for the fuel its boilers used during the downtime. If you are studying performance while the optimiser was active, identify the period separately and explain how you treated it. Give both comparisons cleardates, so a reader knows exactly what the figures cover. A single headline percentage has less value to finance if the operating period behind it is unclear.
Check What Changed Besides the Weather
Ask the estates team whether the building delivered the same service before and after the work. A school timetable can shift, a wing can reopen after refurbishment or holiday use can change. Those events matter even when you compare months with a similar number of degree days. Check the heating schedule and maintenance log alongside the bills. Changes to operating hours, temperature settings and manual controls can influence the result over time. Commercial boiler operation guide
Keep a dated note of other energy measures, including control work or insulation, if they fall inside the comparison period. The meter can show how much less gas was used across all the equipment it serves. If several measures took effect together, consider what evidence you have to attribute a share to each one. If the available evidence covers the combined works, identify the result as a combined saving and record which measures contributed.
A change in plant can make the baseline less reliable. If a boiler was replaced just before the trial, readings for the old plant may poorly guide the gas the new equipment would ordinarily use. Build a reference period that reflects the equipment and operating arrangements under review. If that leaves you with only a few months of records, give finance a date for the next review and explain the conditions the current evidence covers.
A useful early check is to look at the variation in ordinary baseline months. If two months with similar weather already show very different gas use, ask whether school holidays, weekend opening or hot water demand accounts for the gap. Record the explanation where the records support it. An apparent saving needs to be large enough to be interpretable against that normal variation.
Use the Savings Report Alongside the Meter
Optiburner is a retrofit that adjusts the firing pattern of a commercial boiler. When demand permits, the system uses more of the heat already held in the circuit before the burner fires again. Fewer, slightly longer burns can reduce total firing time while meeting heating demand. Optiburner compares burner operation with and without optimisation every 50 cycles and provides the recorded information in a downloadable Savings Report.
A plantroom report gives you a view of the boilers under assessment and helps show when their firing patterns changed. Use it alongside the gas meter, which captures the fuel consumed by the equipment on that supply. If the report shows a change in firing time, check that the gas comparison covers the same operating conditions and that the building continued to receive the space heating and hot water it needed. Treat each record according to what it measures.
An unusually warm month may give you limited evidence about how the plant behaves at higher demand. Review the results through the heating season if you want a view of typical running conditions. Keep a copy of the reports, readings, and changes made to the plant so a second person can see how the estimate was built. A consistent record is particularly helpful when the team changes contractors or hands the project from estates to finance.
Present the Saving So Finance Can Check It
In the review, show actual gas use, weather-adjusted expected use and the difference in kWh. Record the meter scope, period and any operational changes that affected the result. Explain how you represented months with an estimated reading or a change in service. Estimate the cash value of the fuel saving at a stated unit rate and keep any change in standing charges separate from the consumption saving.
If the weather adjustment leaves a residual saving, show how sensitive the result is to assumptions the estate’s records cannot verify. A simple check is to revisit the estimate of steady hot water demand and see how much the adjusted result changes. Record which assumption matters most. That tells the team where a longer data series or a dedicated reading would improve its confidence.
Put the result in the context of what the building needed throughout that period. If a school ran extra evening sessions, there may be fewer directly comparable months. If a maintenance event interrupted optimisation, the report should make that visible. With those details in place, a finance director can see both the saving and whether the comparison is a sound basis for a forward budget.
Agree How You Will Test the Result
Discuss your verification plan with the Optiburner team while you still have access to the pre-installation plant records. Bring one period where you have actual gas readings and operating dates, and flag any planned changes to the way the building is heated. The team can help you decide how the boiler’s Savings Report would sit alongside the meter analysis.